Dead Tank Circuit Breakers up to 800 kV
Flexible, high performance breaker technology
The 800 kV Dead Tank Circuit Breakers (DTB) can be equipped with pre-insertion resistors and are tested for high transient recovery voltage (TRV) performance, high mechanical endurance and switching capabilities. Installation time is greatly reduced due to control wire bundling.
For shunt reactor protection, Hitachi Energy offers Dead Tank Circuit Breakers with applied, internal Metal Oxide Varistors (MOVs). This solution increases the reliability of the breaker by limiting damaging overvoltage’s.
Applications
- Line, transformer, reactor and capacitor switching
- Point-on-wave switching
- High seismic applications
- High altitude applications
Why Hitachi Energy?
- Flexible design platform provides options for pre-insertion resistors and various height-to-live part configurations
- High TRV withstand for long transmission lines
- High current potential facilitates high load transmission
- Short installation time due to factory pre-assembly
- Widely installed base in all environments and applications
- Global service organization, local everywhere
Brief performance data
DTB up to 800 kV |
|
800PM |
---|---|---|
Rated voltage |
kV |
800 |
Short-circuit breaking current |
kA |
40-63 |
Rated current |
A |
up to 5000 |
Interrupting time |
cycles |
2 |
Closing and latching current |
kA |
104-164 |
Lightning impulse withstand level - LIWL |
kV |
2050 |
Operation type* |
Single-pole operated |
|
Operating mechanism |
HMB-8 |
* Single-pole operation also referred to as independent pole operation.